- 1272 -
10.2.36 Supervision of communication setting (Commslv error)
A setting error can be detected if contradictory data has been set in the memory. Error
messages are shown depending on a kind of the communication protocols.
(i) Error level
The default error level has set at level 3 (Minor error), but the user can change it using setting
[CHK_CMLV:LVl]; and then, set On for the setting [CHK_CMLV:Sw]. Errors can be detected in
two minutes after the IED switches on.
(ii) Error message
When detecting errors, an error message can be shown on the LCD screen and an LED turns
on.
Table 10.2-73 Error messages provided by the supervisor in CHK_CMLV
Meaning of the information
Detection of the failure in the settings
(iii) Setting error information
If a signal mapping has not been performed correctly, error messages be shown in Hexadecimal
codes.
Table 10.2-74 61850 setting error information in CHK_CMLV
Meaning of the detailed information
0001xxxx: IEC61850 error
0010xxxx: IEC60870-5-103 error
Number (high-order) of Data ID
mistakenly be mapped in the IED
Number (low-order) of Data ID
mistakenly be mapped in the IED
Figure 10.2-1 Sample error message
Note: Figure 10.2-1 is an example of 61850 error; and the content of that can be
different depends on degree errors; hence, this is just an example:
• The first of the top left part (i.e., “0001”) is showing the error belongs to
Data(cmmslv) error
10:48 1/1
[Minor error]
[00010004] [51200131]
[03011001] [4747494F]
[32245354] [7456616C]