6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 147 -
To TRC
To DISCAR
≥1
SOTF-Z1G-OPT
SOTF-Z1XG-OPT
SOTF-Z2G-OPT
SOTF-Z3G-OPT
SOTF-Z4G-OPT
SOTF-Z5G-OPT
SOTF-Z1G-OPT-A
SOTF-Z1G-OPT-B
SOTF-Z1G-OPT-C
SOTF-ZG-OPT-AR
SOTF-ZG-OPT-BR
SOTF-ZG-OPT-CR
≥1
SOTF-ZG-OPT-TRIP
From Z1G to Z5G logics
SOTF-ZG-ARC-BLOCK
SOTF-Z1XG-OPT-A
SOTF-Z1XG-OPT-B
SOTF-Z1XG-OPT-C
SOTF-Z2G-OPT-A
SOTF-Z2G-OPT-B
SOTF-Z2G-OPT-C
SOTF-Z3G-OPT-A
SOTF-Z3G-OPT-B
SOTF-Z3G-OPT-C
SOTF-Z4G-OPT-A
SOTF-Z4G-OPT-B
SOTF-Z4G-OPT-C
SOTF-Z5G-OPT-A
SOTF-Z5G-OPT-B
SOTF-Z5G-OPT-C
≥1
≥1
8800001B81
8900001B82
8A00001B83
8300001B28
Figure 2.10-52 SOTF-ZG grouping logic for TRC/Recording functions
TRIP commands for opening the CB poles
The ZG function issues a per-phase trip signal so that a per-phase TRIP COMMAND will be
generated in the TRC function; set a single-phase trip (1P) mode for scheme switch [Z*G-TPMD].
The user can also set a three-phase trip (3P) mode if the TRIP_COMMANDs does not need to
issue separately. Note that the TRIP_COMMANDs will be issued for the CB in the TRC
function after collecting signals from the other functions. Remember that the user should set
1-PHASE for the scheme switch [TP-MODE] in the TRC for 3P mode. The user should recognize
that the settings of the [Z*G-TPMD] (see Figure 2.10-45 etc. and Figure 2.10-51) and the setting
[TP-MODE] (see Figure 2.33-3) have cooperation to trip the CB correctly.
Note: For your information, the settings of TRC function affect the other trip signals
from other functions. See
Chapter Relay application: Trip circuit
.