6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 613 -
Table 3.8-4 Mapping signals for MOD object.
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
System/LLN0$Mod$origin
orCat
orCategory
ST
5500013013011000
MDCTRL01_ORCAT
System/LLN0$Mod$origin
orIdent
Octet64
ST
5500016A13011009
MDCTRL01_ORIDENT
System/LLN0$Mod
stSeld
BOOLEAN
ST
5500010013011D90
MDCTRL01_SLD_RPT
Drag and drop
Figure 3.8-4 orCat attribute mapped into MOD object of LLNO
(iii) Mapping input data
The MDCTRL01 function can receive three commands select, operate, and cancel. Thus, the
user should map the input-point MDCTRL01_CONTROL_REQ. Table 3.8-5 shows the input-
point MDCTRL01_CONTROL_REQ and the Object reference System/LLN0$Mod$; the user
should map the Object reference having attributes CO and CF in FC to the input-point. Note that
the user should map the input-point to all attributes having CO and CF. Figure below shows
how to map a signal.