4.2.2 Cancel logic for SBO mode
In the SBO control mode, the reception of a cancel command is possible; when the cancel
conditions are satisfied, accordingly, the IED can discard the select command; finally, the
operation returns to the initial stage (i.e., “Wait for a command”.)
(i) Receiving “Cancel” from the remote-end
Figure 4.2-14 depicts the cancel command procedure for a cancel command initiated from the
remote-end.
Signal reception in
IEC61850
Cancel from the remote-end
Cancel from the local-end
Select command Open from the remote-end
Select command Closing from the remote-end
Select command Open from the local-end
Select command Closing from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.2-14 Outline of ‘cancel’ command from the remote-end
Input point required mapping
Figure 4.2-15 depicts the cancel logic when a “Cancel command (Remote-Cancel)” signal is
applied to the DPSY01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the signal “Select command Closing (Remote-Closing-Control)”.
DPSY01 function (Function ID: 511001)
“DPSY01_ CC_SS” (511001
8602011E95)
“DPSY01_CC_FS”
(511001 8702011E96)
Figure 4.2-15 ‘Cancel’ from the remote-end in DPSY01