6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 918 -
Input
Output
Selection logic in TPOS01
Command Local-P3-Control
TPOS1-P3
ILK condition (“P3”) passed
ILK bypassing
1≥
ICB_STATE
[TPOS01-CTRAHMI]
SBO
TPOS01 function (Function ID: 513001)
SBO
DIR
&
&
1≥
&
0.1s
0
t
0.6s
0
t
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
Select condition
TPOS01_P3SL_BO_FLG
(513001_8A04011DC8)
Select Failed
To BO connection
Select success
To Wait for a command
Select command
with ILK condition
Operat command
with ILK condition
For SBO operation
For DIR operation
Figure 4.9-13 Select ‘P3-control’ on the front panel in TPOS01
††
Note: The ILK function provides the operation criteria for P3-control”.
††
Note: To identify the input/output signals of the other TPOS logics, see Table
4.9-6,Table 4.9-7 , and Table 4.9-10.
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
Output signal to BO
When the select condition” signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P3SL_BO_FLG.
1
Note: The “TPOS01_P3SL_BO_FLG signal is the same signal as shown in Figure 4.9-7.
If the Local-P3-Control” signal is not true, the TPOS01 function returns to the
Wait for a command stage.
(vii) Receiving “Select command P1-control” by PLC function