(v) Receiving “Select command On” by PLC function
Figure 4.8-9 outlines the reception of the select command On by the PLC function.
PLC logic programmed
by the user
Select command On by PLC function
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Off from the remote-end
Select command Off by the PLC function
Select command On from the remote-end
Select command Off from the local-end
Select command On from the local-end
Figure 4.8-9 Outline of Select command On
Input signal from the PLC function
Figure 4.8-10 shows the Select logic when a select command On (PLC-On-Control)” signal is
generated by the PLC function. There are two input points for reception of this signal: the
former connection point, (PLC#1) is used for the reception of the select-command requiring the
interlock check, the later connection point, (PLC#2) is used for the reception of the select-
command not requiring the interlock check. That is, for the DPOS01 function, when the “Select
command On (PLC-ON-Control)” signal generated in the user-programmed logic is applied for
the select logic and when the interlock check is required in the select logic, use the connection
point (PLC#1: e.g.DEV01_CL_INTERLOCK). Alternatively, if the interlock check is not
required, use the other connection point (PLC# 2: e.g., DEV01_CL_COMMAND) for the
injection. PLC#1 and PLC#2 is shown in Table 4.8-2.
Output signal to BO
The DPOS01 function, in Figure 4.8-10, can issue a “Select success” signal at the output-point
DPOS01_OSL_BO_CSF”
1
.
1
Note: The DPOS01_OSL_BO_CSF” signal is the same signal as that shown in Figure
4.8-2.