6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 851 -
DPOS01 function (Function ID: 512001)
DEV01_CL_INTERLOCK
Operate command
without ILK condition
ILK condition (“ON”) passed
PLC in DIR operate
512001 800301EE33
DPOS01-Close
Signals from user-PLC logic
Output
Select logic in DPOS01
0.1s
0
t
0.6s
0
t
&
&
&
Select condition
1
ON-control command requiring ILK checking
(PLC #1 connection point)
DEV01_CL_COMMAND
512001 800301EE32
ON-control command requiring no ILK† checking
(PLC#2 connection point)
Operate command
with ILK condition
For DIR operation
For DIR operation
DPOS01_OSL_BO_CSF
(512001_8603011DC6)
Select Failed
To BO connection
Select success
To Wait for a command
To Wait for a next
command
Figure 4.8-10 Select ‘On using the PLC function in DPOS01
††
Note: The software interlocking (ILK) function provides the operation criteria for “On”.
The ILK function is discussed separately; note that the operation criteria is
defined in the ILK function itself (i.e., the user cannot set the condition).
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.8-13.
††
Note: To identify the input and output points of the other DPOS logics, see Table 4.8-2
for the inputs (PLC#1 and PLC#2) and Table 4.8-9 for the outputs.