EasyManua.ls Logo

Toshiba GR200 Series - 2.7.5 Nature of CT saturation in case of external fault

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 83 -
2.7.5 Nature of CT saturation in case of external fault
Figure 2.7-12 shows that an external fault occurs out of the protected line GH. In the DIFL
function the magnitude of an entering current (I
G
) is approximately equal to the one of a
leaving current (I
H
). Thereby, the error made by the CT saturation can be offset in the DIFL
calculation, if both CTs have the same characteristic.
Terminal-G
Fault
Terminal-H
I
G
I
H
Terminal-G
Fault
Junction-J
Terminal-H
Terminal-K
I
G
I
K
I
H
Figure 2.7-12 CT saturation induced by an external fault beyond the protected line
On the other hand, as shown in Figure 2.7-13, if an external fault occurs beyond the
terminal-H, the DIFL function applied for the three-terminal line cannot offset the error. This
is because the same magnitude of the fault current does not flow at respective terminals; the
terminal-H, which is in close proximately the external fault, may experience the outflowing
fault current larger than the terminal-G and the terminal-K. In other words, the DIFL function
cannot offset the error yielded by the CT saturation, unlike in the above case. Thus, the user
has to check a case that CT saturation is particularly produced in when a terminal has an
outflow; the CT saturation must be accommodated utilizing the DIFI2 setting in the DIFL
function.
Terminal-G
Fault
Terminal-H
I
G
I
H
Terminal-G
Fault
Junction-J
Terminal-H
Terminal-K
I
G
I
K
I
H
Figure 2.7-13 CT saturation induced by an external fault on a three-terminal line

Table of Contents

Related product manuals