EasyManua.ls Logo

Toshiba GR200 Series - (ii) Output signal required mapping; (iii) Select condition

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 577 -
and monitoring application: Automatic sequence control function
.
*Note: The LEDR function can run on either the SBO mode or the DIR mode using a
ctlmodel signal when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.
(ii) Output signal required mapping
The LEDR function can issue a Select success signal at the output point
LEDR01_NSD_CSF, when the LEDR function determines that the input signal Select
command (reset) is true. If the LEDR function determines that the LEDR01_NSD_CSF is
not true, the LEDR function returns to the Wait for a next command stage.
(iii) Select condition
Figure 3.6-3 shows the select condition logic in the LEDR function.
Select condition
LEDR function (Function ID: 528001)
To selection logic
Control hierarchy (e.g. 43RL) (PLC connection point) *5
IED serious error detected
[LEDDR1_EN]
On
Users must setup this condition correctly
Function Automatic sequence control is in progress
S4301_STATE
Command blocking*1 (S4301 defines ”Blocked”)
Double Command Blocking detected*2
Other devices traveling detected*3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
LEDR01_CTRL_RIGHT
528001 820701ED50
SERI_ERR
&
&
1
Unmatched condition detected *4
Figure 3.6-3 Select condition logic in LEDR
*6
*1
Note: command blocking disables any operation except its own: the command
blocking is initiated by the status of S4301 in a software controller (SOFTSW).
The IEC 61850 standard defines command blocking as CmdBlk. For more
information on S4301, see Chapter
Control and monitoring application: Software
switch control function
. See the signal S4301_STATE of Table 3.6-2.
*2
Note: “Double Command Blocking (DCB) is an operation philosophy in the
common control function (CMNCTRL). It can be used to protect the substation.
The user can program it using GR-TIEMS. The DCB operating signal is denoted
as “DCB RCV_OR in Table 3.6-2. For more information, see Chapter
Control and
monitoring application: Common controls
.
*3
Note: If the event “device-travelling” is detected in the CMNCTRL function, it
indicates that another operator is changing the status of a device. Thus, the IED
should inhibit the operation of any device for the duration that the event is

Table of Contents

Related product manuals