- 913 -
TPOS01 function (Function ID: 513001)
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
Command “P3-Control” from the remote
ILK† condition (“P3”) passed
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*)
Selection logic in TPOS01
“Automatic sequence control function (AQEQ)§” in progress
Select command
with ILK† condition
Operate command
with ILK† condition
Select command
without ILK† condition
Operate command
without ILK† condition
Figure 4.9-7 Select ‘P3-control’ from the remote-end in TPOS01
††
†Note: The ILK function provides the operation criteria for “P3 control”.
††
Note: To identify the input and output points of the other TPOS logics, see Table 4.9-5,
Table 4.9-7 and Table 4.9-10.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
Output signal to BO
The TPOS01 function, in Figure 4.9-7, can issue a signal “Select success” at the output point
“TPOS01_P3SL_BO_FL” when the TPOS01 function determines that the received signal
“Select command P3 (Remote-P3-Control)” is true. If the TPOS01 function determines that the
“Remote-P3-Control” is not true, the TPOS01 function returns to the “Wait for a command”
stage.