TPOS01 function (Function ID: 513001)
TPOS01_P3SL_BO_FLG
(513001 8A04011DC8)
DEV01_CONTROL_REQ
Command P3-Control from the remote
ILK condition (“P3”) passed
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
In SBO operate
In DIR operate
Select Failed
513001 7004016D08
TPOS1-P3
To BO connection
Input
Output
Selection logic in TPOS01
0.1s
0
t
0.6s
0
t
&
&
&
&
&
Select success
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
Select condition
1
Select command
with ILK condition
Operate command
with ILK condition
Select command
without ILK condition
Operate command
without ILK condition
For SBO operation
For DIR operation
To Wait for a command
For DIR operation
For SBO operation
Figure 4.9-7 Select ‘P3-control’ from the remote-end in TPOS01
††
Note: The ILK function provides the operation criteria for P3 control”.
††
Note: To identify the input and output points of the other TPOS logics, see Table 4.9-5,
Table 4.9-7 and Table 4.9-10.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
Output signal to BO
The TPOS01 function, in Figure 4.9-7, can issue a signal “Select success” at the output point
“TPOS01_P3SL_BO_FL when the TPOS01 function determines that the received signal
Select command P3 (Remote-P3-Control) is true. If the TPOS01 function determines that the
Remote-P3-Control is not true, the TPOS01 function returns to the Wait for a command
stage.