(iii) Select condition
Similar to the select condition (see sec.3.7.2(ii)), the GCNT01 function has an operate-condition
logic. Figure 3.7-14 shows the operate-condition logic.
Operate condition
GCNT01 function (Function ID: 540001)
To operate logic
From Control hierarchy *5
From CMNCTRL
[GCNT01-HMI]
On
Function Automatic sequence control is in progress
Double Command Blocking detected*2
Other devices traveling detected*3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
GCNT00IN_TMP_51
540001 800E00ED5A
SERI_ERR
&
&
1
Unmatched condition detected *4
Serious error detection
From SOTFSW*1
S4301_STATE
Command blocking*1(S4301 defines ”Blocked”)
[DPOS01-EN]
On
Figure 3.7-14 Operate condition logic for GCNT01
15
Note: The signals and settings in Figure 3.7-14 are same as the signals shown in
Figure 3.7-7.
(iv) Signal names and number
Table 3.7-9 PLC monitoring points (Output signal for BIO)
Signal Number
Signal Name
Description
540001 820E011E84
GCNT01_EC_OK_CSCN
GCNT01 execute command OK condition signal
540001 820E021E84
GCNT02_EC_OK_CSCN
GCNT02 execute command OK condition signal
540001 820E031E84
GCNT03_EC_OK_CSCN
GCNT03 execute command OK condition signal
.
.
.
540001 820E201E84
GCNT32_EC_OK_CSCN
GCNT32 execute command OK condition signal