(ii) Recommended setting for the voltage level
As the threshold voltage is expressed with Table 5.5-5, the user should set High or Low to
match to the voltage value to input to PWS. Table 5.5-6 shows the recommended setting.
After that, the user should set the threshold voltage about the picking-up/dropping-off of the
binary input (see Chapter:
Technical description: Binary IO module (BI, BO and BIO)
).
Table 5.5-6 Recommended setting for the voltage level
(a) In the case of DC rated voltage “110-250 Vdc”
Voltage value to
input to PWS
Recommended setting for the voltage level
250V
220V
High
125V
110V
Low
(b) In the case of DC rated voltage “24-60 Vdc”
Voltage value
to input to PWS
Recommendation for setting for the voltage level
60V
48V
High
30V
24V
Low