- 452 -
(vii) Condition logic – setting (TEVLV)
The Condition logic determines the reclosing mode of either SPAR or TPAR by detecting the
tipped-phases if SPAR, TPAR, or SPAR&TPAR mode is selected.
Figure 2.34-17 Condition logic
When a multiphase fault (TRIP-MPH) occurs in the settings [ARC1-MODE]=SPAR, then
CB1_94TT signal is generated so that the function will reach the final trip stage. When a single
phase fault (TRIP-1PH) evolves to a multiphase fault (TRIP-MPH), then the final trip stage is
also induced; a timer [TEVLV] is provided for this purpose. Note that the timer [TEVLV] should
be lower than the dead timers [TSPAR1].
Note that the ‘CB1_94TT’ and ‘CB2_94TT’ signals are unconditionally generated when a
single phase tripping occurs in TPAR.