EasyManua.ls Logo

Toshiba GR200 Series - (vii) Condition logic - setting (TEVLV)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 452 -
(vii) Condition logic – setting (TEVLV)
The Condition logic determines the reclosing mode of either SPAR or TPAR by detecting the
tipped-phases if SPAR, TPAR, or SPAR&TPAR mode is selected.
1
&
TRIP-ANYPH
TRIP-1PH
TRIP-MPH
Initiation
ARC1-S1 IN-PROG
ARC1-MODE=S&T
ARC1-MODE=SPAR+S&T
ARC1-MODE input
Start
&
&
&
&
&
ARC1_SPAR_COND
ARC1_TPAR_COND
SPAR
TPAR
1
&
ARC2-S1 IN-PROG
&
&
&
&
&
ARC2_SPAR_COND
ARC2_TPAR_COND
ARC1-MODE=SPAR
ARC1-MODE=TPAR
&
CB1_94TT
To TRC
MPH-TRIP
IN SPAR1
ARC1-MODE
SPAR
TPAR
SPAR&TPAR
1
ARC2-MODE=S&T
ARC2-MODE=SPAR+S&T
ARC2-MODE=SPAR
ARC2-MODE=TPAR
&
CB2_94TT
&
CB1_94TT
t 0
0.01-300.00s
TEVLV
EVOLV_FAULT
TIME OVER1
8200001B6A
CB2_94TT
&
&
EVOLV_FAULT
TIME OVER2
ARC1 IN-PROG OR
&
&
OFF
FT
MPAR
ORIGINAL
ARC2-MODE input
ARC2-MODE
SPAR
TPAR
SPAR&TPAR
1
OFF
FT
MPAR
ORIGINAL
CB1_94TT
CB2_94TT
ARC1 FT
MPH-TRIP
IN SPAR2
ARC2 FT
ARC1 FT
ARC2 FT
Figure 2.34-17 Condition logic
When a multiphase fault (TRIP-MPH) occurs in the settings [ARC1-MODE]=SPAR, then
CB1_94TT signal is generated so that the function will reach the final trip stage. When a single
phase fault (TRIP-1PH) evolves to a multiphase fault (TRIP-MPH), then the final trip stage is
also induced; a timer [TEVLV] is provided for this purpose. Note that the timer [TEVLV] should
be lower than the dead timers [TSPAR1].
Note that the CB1_94TT and CB2_94TT signals are unconditionally generated when a
single phase tripping occurs in TPAR.