EasyManua.ls Logo

Toshiba GR200 Series - 2.27.1 Operation characteristic

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 351 -
2.27.1 Operation characteristic
Two elements are provided to detect an out-of-step condition. Figure 2.27-1 shows the operation
principle of the OSTV function. Reference voltage (V
A
) is acquired in IED A at terminal A; and
a corresponding voltage (V
B
) is acquired in IED B at terminal B. Using the telecommunication
1
voltage data at both terminals are provided to the respective opposite terminals. Electrical
center is located at which the respective impedances for respective terminals are equal.
Figure 2.27-1 Typical impedance and electrical center
1
Note: The data is transferred by the function of Communication application. For more
information, see Chapter
Relay application: Communication application
.
Figure 2.27-2 is the characteristic of the OSTV-1 element. Phasor V
B
will exist in the
second quadrant (α-zone) or the third quadrant (β-zone) if the out-of-step state is appeared.
This is because a reference voltage is obtained at terminal A.
Figure 2.27-2 Voltage phase comparison between terminal A and terminal B (OSTV-1)
IED A
V
A
V
B
Data of V
B
Telecommunication
Electrical center
Terminal A
Terminal B
Z
A
Z
B
Z
L
(Z
A
+Z
L
+Z
B
)/2
(Z
A
+Z
L
+Z
B
)/2
IED B
Left impedance
Right impedance
Data of V
A
-zone
V
B
-zone
V
A
1V

Table of Contents

Related product manuals