6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 600 -
Signal reception
in the IEC61850
Operate command Reset from the remote-end
Do nothing
Operation
decision
Success
Failed
Operate logic
Wait for a command
Signal output
Wait for a next command
Select stage
Select command
Reset from the
remote-end
Signal reception
from
the front panel
Operate command Reset from the local-end
Do nothing
Operation
decision
Success
Failed
Operate logic
Signal output
Figure 3.7-12 Outline of Operate command ‘Reset’
New counter value
Figure 3.7-13 shows that the user can set a new value for the counter using the statics sub-
menu. The new value is applied into Statics counter point in Figure 3.7-11.
Counter
10:48 1/8
COUNT1 (No Assign) +
0
COUNT2 (No Assign) +
0
COUNT3 (No Assign) +
0
Figure 3.7-13 Counter menu in the statics sub-menu
Note: For the operation, see
Chapter User interface: Monitoring sub-menu
.
Output signal to BO
The GCNT01 function can provide a signal at the point GCNT01_OK_CSC”, when the new
value applied from the sub-menu is appropriate.