6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 998 -
Table 4.11-3 Mapping points for Emergency command
Signal Number
Signal Name
Description
M/O
523001 820D10ED50
EMERSTOP_CONTROL_REQ
Emergency control for stopping the operation
M
Table 4.11-4 PLC connection points (Inputs for stopping ASEQ operation)
Signal Number
Signal Name
Description
M/O
523001 800D01EDF2
ASEQ01_EXEC_RESET
Instruction to stop ASEQ01 operation
O
523001 800D02EDF2
ASEQ02_EXEC_RESET
Instruction to stop ASEQ02 operation
O
523001 800D03EDF2
ASEQ03_EXEC_RESET
Instruction to stop ASEQ03 operation
O
523001 800D0FEDF2
ASEQ15_EXEC_RESET
Instruction to stop ASEQ15 operation
O
Table 4.11-5 PLC monitoring points (Outputs to start ASEQ operation)
Signal Number
Signal Name
Description
523001 820D011F50
ASEQ01_EXEC_START
Start instruction provided for ASEQ01 operation
523001 820D021F50
ASEQ02_EXEC_START
Start instruction provided for ASEQ02 operation
523001 820D031F50
ASEQ03_EXEC_START
Start instruction provided for ASEQ03 operation
523001 820D0F1F50
ASEQ15_EXEC_START
Start instruction provided for ASEQ15 operation
Table 4.11-6 PLC monitoring points (Outputs to stop ASEQ operation)
Signal Number
Signal Name
Description
523001 810D011F51
ASEQ01_EXEC_STOP
Stop instruction provided for ASEQ01 operation
523001 810D021F51
ASEQ02_EXEC_STOP
Stop instruction provided for ASEQ02 operation
523001 810D031F51
ASEQ03_EXEC_STOP
Stop instruction provided for ASEQ03 operation
523001 810D0F1F51
ASEQ15_EXEC_STOP
Stop instruction provided for ASEQ15 operation
Table 4.11-7 PLC monitoring points (Outputs of ASEQ operation status)
Signal Number
Signal Name
Description
523001 000D011001
ASEQ01_ACC_EXEC
Status of ASEQ01 operation
523001 000D021001
ASEQ02_ACC_EXEC
Status of ASEQ02 operation
523001 000D031001
ASEQ03_ACC_EXEC
Status of ASEQ03 operation
523001 000D0F1001
ASEQ15_ACC_EXEC
Status of ASEQ15 operation
4.11.2 Preparation of the operation
The ASEQ01 function has three scheme switches: [ASEQ01-EN], [ASEQ01-CTRMENU] and
[ASEQ01-CTRAHMI].
The scheme switch [ASEQ01-CTRMENU] is used for a local operation (e.g., the front panel
operation on the IED). When On is set for the scheme switch [ASEQ01-CTRMENU], the PLC
sequence #1 can be instructed locally. The scheme switch [ASEQ01-CTRAHMI] is used to select
either a select-before-operation command (SBO) or a direct command (DIR) when the local