EasyManua.ls Logo

Toshiba GR200 Series - (vi) Receiving “Select command Open” by PLC function; (vi)-1 Input signal from the PLC function; (vi)-2 Output signal to BO

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 680 -
(vi) Receiving “Select command Open” by PLC function
Figure 4.2-11 outlines the reception of the select command Open by the PLC function.
PLC logic programmed
by the user
Select command Open by the PLC function
Signal output
Select
decision
Success
Failed
Select logic
Select stage
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Open from the remote-end
Select command Closing from the remote-end
Select command Open from the local-end
Select command Closing from the local-end
Select command Closing by the PLC function
Figure 4.2-11 Outline of select command Open
Input signal from the PLC function
Figure 4.2-12 shows the select logic when a “Select command Open (PLC-Open-Control)” signal
is generated by the PLC function There are two input-points for the reception of this signal,
unlike in the signal “Select command Closing (PLC-Closing-Control)” where four are available.
That is, if interlock checking is required, use the connection point (PLC#1:e.g.,
DEV01_OP_INTERLOCK). Alternatively, if the interlock check is not required, use the
connection point (PLC#2:e.g., DEV01_OP_COMMAND). PLC#1 and the PLC#2 are shown in
Table 4.2-4.
DPSY01 function (Function ID: 511001)
DPSY01_FSL_BO_CSF
(511001_8A02011DC4)
DEV01_OP_INTERLOCK
Operation command
without ILK condition
ILK condition (“Open”) passed
PLC in DIR operate
For DIR operation
511001 800201EE31
Signals from user PLC logic
Output
Select logic in DPSY01
0.1s
0
t
&
&
&
Select condition
1
Open-control command requiring ILK checking
(PLC#1 connection point)
DEV01_OP_COMMAND
511001 800201EE30
Open-control command requiring no ILK checking
(PLC#2 connection point)
Operation command
with ILK condition
DPSY01-Open
Select Failed
To BO connection
Select success
To Wait for a command
For DIR operation
Figure 4.2-12 Select Open by PLC function in DPSY01
††
††
Note: To identify the input and output points of the DPSY02 logic, see Table 4.2-4 for
the inputs (PLC#1 and PLC#2) and Table 4.2-11 for the outputs.
Output signal to BO

Table of Contents

Related product manuals