4.1.2 Cancel logic for SBO mode
In SBO control mode the reception of a cancel command is possible; the function can discard
the select command when the cancel conditions are satisfied; finally, the operation returns to
the initial stage (i.e., waiting state Wait for a command.)
(i) Receiving “Cancel” from the remote-end
Figure 4.1-14 depicts the cancel command procedure for a cancel command initiated from the
remote-end.
Signal reception in
IEC61850
Cancel from remote-end
Do nothing
Cancel
decision
Success
Failed
Cancel logic
Wait for a command
Operate logic
Operate command
Operate logic
Select logics
Cancel from front panel
Select command Off from remote-end
Select command On from remote-end
Select command Off from front panel
Select On from front panel
Select command On by the PLC
function
Select command Off by the PLC
function
Wait for a next command
Figure 4.1-14 Outline of ‘cancel command from the remote-end
Input point required mapping
Figure 4.1-15 depicts the cancel logic when a Cancel command (Remote-Cancel) signal is
applied to the SPOS01 function. The input-point “DEV01_CONTROL_REQ” is the same as
that for the signal Select command On (Remote-On-Control).
SPOS01 function (Function ID: 510001)
“SPOS01_ CC_SS (510001_8601011E95)
DEV01_CONTROL_REQ
Cancel command
Command Remote-cancel
510001_7001016D08
510001 7001016D08
Input
Output
Cancel logic in SPOS01
Cancel condition
&
&
Successes to cancel
Operation Failed
“SPOS01_CC_FS (510001_8701011E96)
Do nothing
To Wait for a command
Figure 4.1-15 ‘Cancel’ from the remote-end in SPOS01
Note: The logic cancel conditionis shown in Figure 4.1-18
Output signal to BO
The SPOS01 function can issue an output signal Success to cancel at the monitoring point
SPOS01_CC_SS, when the SPOS01 function has determined that the Remote-cancel signal