EasyManua.ls Logo

Toshiba GR200 Series - (iii) Setting; (iv) Signal (Data ID)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1113 -
Binary input circuits BI1 to BI3
at IO#3 (IO_SLOT1)
DOUT_BOOL
FID
DTYPE
DID
ST
DI
DOUT_UNIT
FID
DTYPE
DID
ST
DI
Unit#16#201400
Unit#16#31
Unit#16#4000E1A0
PLC basic-function
(SEL)
A group number enters
to Setting function
(Function ID: 201400)
DIN_BOOL
FID
DTYPE
DID
ST
DO
UDINT#16#200B03
UDINT#16#80
UDINT#16#01001111
BI3_1
DIN_BOOL
FID
DTYPE
DID
ST
DO
UDINT#16#200B03
UDINT#16#80
BI3_2
UDINT#16#01011111
DIN_BOOL
FID
DTYPE
DID
ST
DO
UDINT#16#200B03
UDINT#16#80
BI3_3
UDINT#16#01021111
BOOL_TO_UNIT
BOOL_TO_UNIT
BOOL_TO_UNIT
ADD
UDINT#16#2
MUL
UDINT#16#4
MUL
ADD
ADD
UDINT#16#1
DOUT_UNIT_1
TON
IN
PT
Q
ET
Delay time#
XX ms
TON
IN
PT
Q
ET
Delay time#
XX ms
TON
IN
PT
Q
ET
Delay time#
XX ms
PLC basic-function
(Ondelay)
Figure 5.8-3 Logic for changing a group setting
(iii) Setting
PF (Function ID: 201400) at Setting|Protection
Setting items
Range
Unit
Contents
Default
Note
Active Group
1 to 8
Selection of a setting group number
1
(iv) Signal (Data ID)
Connection point on PLC logic
Setting_PF (Function ID: 201400)
Element ID
Name
Description
314000E1A0
PLC_Group_ENUM
Reception for setting group number
Signal monitoring points
Setting_PF (Function ID: 201400)
Element ID
Name
Description
3200001001
ACT_GRP
3010011001
COM_CHG
3010031001
CTRL_CHG
3010021001
PRO_CHG
3010001001
SYS_CHG

Table of Contents