relay. If the setting value (signal No.) is “0”, all setting items related events are disable and
the frame is not provided.
†Note: A relevant Data ID is required to select; the description is obtained
automatically.
Type ID
Type ID=1 (Time-tagged message) or Type ID=2 (Time-tagged message with relative time)
is selected to set the frame type. It is recommended that the frame related to status is set
to Type ID=1 and the frame related to faults is set to Type ID=2. In Type ID=2, the trigger
signal for the relative time should be set. For the setting, see Section 11.4.5(i).
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided, the INF according to the Appendix† is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-5 and the
Appendix†.
Table 11.4-5 INF category of Monitor direction
†Note: See
Appendix: IEC 60870-5-103 interoperability: Semantics of Information
number.
FUN
Function type (FUN) is set referring to Table 11.4-6. The FUN can be set to 0 to 255. When
clicking the “Change all FUNs” on the Common setting screen, all FUNs are changed to the
setting values at Common setting.
Table 11.4-6 Semantics of Function type
transformer differential protection
Line differential protection