EasyManua.ls Logo

Toshiba GR200 Series - 2.14.2 Setting; 2.14.3 Data ID

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 219 -
2.14.2 Setting
SOTF-OC(Function ID: 454001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
SOTFOC-EN
Off / On
-
SOTF-OC protection enable
Off
OCSOTF
0.02 -
3.00
0.10 -
15.00
A
OC relay for SOTF threshold
1.20
6.00
OCSOTF-2fBlk
Non / Block-3P /
Block-PerP
-
OCSOTF operation block by 2f-detection
Non
Test tool (Function ID: 454001)
Item
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Function test
SOTF-Test
Off / On
-
Test cold load state given with setting
Off
2.14.3 Data ID
Monitoring point for operation
SOTF-OC(Function ID: 454001)
Element ID
Name
Description
8000001BB2
ADD.SOTF_EN
Additional SOTFOC enable
8000001B67
OC-RETRIP
OC-RETRIP
8000001BB1
OC-RTP.EN
OC-retrip enable
8000001C20
OCSOTF-A
SOTFOC relay element operated (phase-A)
8100001C21
OCSOTF-B
SOTFOC relay element operated (phase-B)
8200001C22
OCSOTF-C
SOTFOC relay element operated (phase-C)
8000001B60
OCSOTF-OR
SOTFOC relay element operated (3-phases OR)
8000001B66
SOTFOC-OPT
SOTFOC protection operated (3-phases OR)
8800001B62
SOTFOC-OPT-A
SOTFOC protection operated (phase-A)
8900001B63
SOTFOC-OPT-B
SOTFOC protection operated (phase-B)
8A00001B64
SOTFOC-OPT-C
SOTFOC protection operated (phase-C)
8300001B23
SOTFOC-TRIP
Trip signal by SOTFOC protection operation
8000001BB0
SOTFOC_BLOCK
SOTFOC protection block command
8000001B65
SOTF_EN_COND
SOTFOC protection operated permit
Connection point on PLC logic
SOTF-OC(Function ID: 454001)
Element ID
Name
Description
800000EBB2
ADD.SOTF_EN
Additional SOTFOC enable
800000EBB1
OC-RTP.EN
OC-retrip enable
800000EBB0
SOTFOC_BLOCK
SOTFOC protection block command

Table of Contents

Related product manuals