- 677 -
(iv) Receiving “Select command Open” from the local-end
Figure 4.2-7 outlines the reception of the select command ‘Open’ from the local-end.
Signal reception
from the front panel
Select command Open from the local-end
Select command Closing from the remote-end
Select command Closing from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Select command Open from the remote-end
Figure 4.2-7 Outline of select command ‘Open’
Input signal generated at the local-end
Figure 4.2-8 shows the select logic when a “Select command open (Local-Open-Control)” signal
is applied to the DPSY01 function. The signal is provided when the user presses a “Selection
for Open” key on the IED front panel; the user is not required to map the signal from IEC61850
communication.
Selection logic in DPSY01
Command “Local-Open-Control”
DPSY01 function (Function ID: 511001)
ILK condition (“Open”) passed
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850)
“Automatic sequence control function (ASEQ§)” in progress
“DPSY01_FSL_BO_FLG”
(511001 8A02011DC4)
Selection command
with ILK condition
Operation command
with ILK condition
Figure 4.2-8 Select ‘Open’ on the front panel in DPSY01
††
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.2-13.
§Note: An Automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The DPSY01 operation is blocked for the ASEQ function when