6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1135 -
(ii) Sample DTT logics
Figure 7.4-11 shows the DTT1 PLC logics where the BI signal is given to the DIN module; the
output (DO) is connected to the input (DI) of the DOUT module in the COMM_APPL function.
The COM1-1 signals from the remote should be connected with the DTT1 function.
N=1 Frame
Ext.TRIP
BI1
(200B01 8001001110)
DOUT_BOOL
FID
DTYPE
DID
ST
DI
COM_1_S
COM1-1_S
4A9001 800212EBB0
DIN_BOOL
FID
DTYPE
DID
DO
ST
DTT1 logic
COM1-1_R1
COM1-1_R1
(4A9001 801005CF0)
DOUT_BOOL
FID
DTYPE
DID
ST
DI
R1.DTT1
R1.DTT1
485001 800001EBB0
DIN_BOOL
FID
DTYPE
DID
DO
ST
DTT1 logic
COM1-1_R2
COM1-1_R2
(4A9001 801007C78)
DOUT_BOOL
FID
DTYPE
DID
ST
DI
R2.DTT1
R2.DTT1
485001 810001EBB1
DIN_BOOL
FID
DTYPE
DID
DO
ST
TRIP_ADD
4A0001 830000EBB5
GE N.TRIP
Figure 7.4-11 Sample logics for DTT1 function at terminals
Note: DIN_BOOL and DOUT_BOOL are used to import and export the information for
the data ID in bit type.