2.2.2 Check relays characteristics (OCs and UVs)
Figure 2.2-4 Check relays logic
†Note: UVD-DIFL element and signal are programmed with settings [DUV-DIFL] etc.
Refer to (v).
‡Note: The user should set Off for the scheme switch [DIFLFS-EN] when the operation of
check relays is not required.
To remove unnecessary operations in the DIFL function, check relays are introduced and
the DIFL function is allowed to operate during the check relays being in operation. The check
relays consists of five relay elements, a signal aggregated with the five relay elements is
injected into the DIFL logic, as shown in Figure 2.2-4. The user should set On for scheme