6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 920 -
TPOS01 function (Function ID: 513001)
DEV01_P1_INTERLOCK
Operate command
without ILK condition
ILK condition (“P1”) passed
PLC in DIR operate
513001 800401EE31
510001 7001016D08
TPOS1-P1
Signals from user-PLC logic
Output
Selection logic in TPOS01
0.1s
0
t
0.6s
0
t
&
&
&
Select condition
1
P1-control command requiring ILK† check
(PLC connection point #1)
DEV01_P1_COMMAND
513001 800401EE30
P1-control command not requiring ILK† checking
(PLC connection point #2)
Operate command
with ILK condition
For DIR operation
For DIR operation
TPOS01_P1SL_BO_FLG
(513001 8A04011DC4)
Select Failed
To BO connection
Select success
To Wait for a command
To Wait for a next
command
Figure 4.9-15 Select ‘P1-control’ by the PLC function in TPOS01
††
Note: The ILK function provides the operation criteria for P1-control”.
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.9-20.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
*Note: The TPOS01 function can run in either the “SBO mode or the “DIR mode. The
user can use signal called ctlmodel when communication is implemented using
IEC61850. To use this signal, the user must map for IEC61850 communication.
††
Note: To identify the input and output point of the other TPOS logics, see Table 4.9-8
for the inputs PLC#1 and PLC#2, Table 4.9-10 for the outputs.
Output signal to BO
The TPOS01 function, in Figure 4.9-15, can issue a “Select success” signal at the output-point
“TPOS01_P1SL_BO_FLG
1
.
1
Note: The “TPOS01_P1SL_BO_FLG signal is the same as the signal shown in Figure
4.9-13.
(viii) Receiving “Select command P2-control” by PLC function
Figure 4.9-16 outlines the reception of the select command P2-control by the PLC function.