- 920 - 
 
TPOS01  function  (Function  ID:  513001) 
Operate command 
without ILK† condition 
ILK† condition (“P1”) passed 
Signals from user-PLC logic   
Selection logic in TPOS01 
P1-control command requiring ILK† check 
(PLC connection point #1) 
P1-control command not requiring ILK† checking 
(PLC connection point #2) 
Operate command   
with ILK† condition 
  “TPOS01_P1SL_BO_FLG” 
(513001 8A04011DC4) 
To “Wait for a next 
command” 
 
Figure 4.9-15 Select ‘P1-control’ by the PLC function in TPOS01
†† 
†Note: The ILK function provides the operation criteria for “P1-control”.   
‡Note: A “select condition” signal is provided from the select condition scheme. For more 
information, see Figure 4.9-20. 
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for 
automatic control. The TPOS01 operation is blocked for the ASEQ function when 
it is in operation. For more information regarding the ASEQ function, see Chapter 
Control and monitoring application: Automatic sequence control function
. 
*Note: The TPOS01 function can run in either the “SBO mode” or the “DIR mode”. The 
user can use signal called “ctlmodel” when communication is implemented using 
IEC61850. To use this signal, the user must map for IEC61850 communication. 
††
Note: To identify the input and output point of the other TPOS logics, see Table 4.9-8 
for the inputs PLC#1 and PLC#2, Table 4.9-10 for the outputs. 
 
  Output signal to BO 
The TPOS01 function, in Figure 4.9-15, can issue a “Select success” signal at the output-point 
“TPOS01_P1SL_BO_FLG”
1
. 
1
Note: The “TPOS01_P1SL_BO_FLG” signal is the same as the signal shown in Figure 
4.9-13. 
 
(viii)  Receiving “Select command P2-control” by PLC function 
Figure 4.9-16 outlines the reception of the select command ‘P2-control’ by the PLC function.