6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 978 -
Table 4.9-38 Mapping signals for ISCSO object
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
Ctrl/GGIO2701$ISCSO$origin
orCat
orCategory
ST
513001 3104011008
TPOS01_ORCAT
Ctrl/GGIO2701$ISCSO$origin
orIdent
Octet64
ST
513001 6A04011009
TPOS01_ORIDENT
Ctrl/GGIO2701$ISCSO
stVal
INT32
ST
513001 3104011001
TPOS01_STATE
Ctrl/GGIO2701$ISCSO
q
Quality
ST
513001 3104011005
TPOS01_QUALITY
Ctrl/GGIO2701$ISCSO
t
Timestamp
ST
513001 9004011006
TPOS01_TIMESTAMP
Ctrl/GGIO2701$ISCSO
stSeld
BOOLEAN
ST
513001 0004011D90
TPOS01_SLD_RPT
Note: Status (ST) is defined in the function constraint (FC) of the IEC 61850 standard.
Drag and drop
Figure 4.9-67 ocCat attribute mapped for ISCSO object of GGIO2701
(iii) Mapping input data
The TPOS01 function can receive three commands select, operate, and cancel. Thus, the user
should map the input-point DEV01_CONTROL_REQto the IEC61850 communication. Table
4.9-39 shows the input-point DEV01_CONTROL_REQ and the Object reference
Ctrl/GGIO2701$ISCSO; the user should map the input-point to the Object references having
attributes CO and CF. Figure 4.9-68 shows how to map a signal.
Note: The attribute is defined in the IEC 61850 standard; CO stands for Control
and CF stands for Configuration in the functional constraint (FC).