Figure 4.9-61 Contact health check setting and EDS scheme for example #1
Setting for erroneous in contact health check (improper setting, example #2)
Figure 4.9-62 shows a setting example for an improper setting of the 43S/EDS scheme. The
settings are implemented incorrectly as shown in Table 4.9-32, BO1-RB is not chosen, instead
BO1 is actually chosen, which is incorrect. In this case, the setting [TPOS01-SLBORD] is
meaningless; hence, the issue of a select command is blocked.