6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 972 -
Plus (+)
TPOS01_P1SL_BO_FLG
(513001 8A04011DC4)
P1
driven
with
BO1
and
BO4
BO1
Drivers
P1-select
command
BO1-RB
(200B01 8002001113)
BO4
P1-operate
command
TPOS01_P1EX_BO
(513001 8104011DD0)
BO4-RB
(200B01 8302031113)
Remote/Local-end
P1-Operate
P1-Selection
BIO module
P2-Operate
P2-Selection
P3-Operate
P3-Selection
Minus ()
TPOS01_P2SL_BO_FLG
(513001 8A04011DC6)
BO2
P2-select
command
BO2-RB
(200B01 8102011113)
BO5
P2-operate
command
TPOS01_P2EX_BO
(513001 8204011DD3)
BO5-RB
(200B01 8402041113)
TPOS01_P3SL_BO_FLG
(513001 8A04011DC8)
BO3
P3-select
command
BO3-RB
(200B01 8202021113)
BO6
P3-operate
command
TPOS01_P3EX_BO
(513001 8204031DD3)
BO6-RB
(200B01 8502051113)
EDS
Figure 4.9-61 Contact health check setting and EDS scheme for example #1
Setting for erroneous in contact health check (improper setting, example #2)
Figure 4.9-62 shows a setting example for an improper setting of the 43S/EDS scheme. The
settings are implemented incorrectly as shown in Table 4.9-32, BO1-RB is not chosen, instead
BO1 is actually chosen, which is incorrect. In this case, the setting [TPOS01-SLBORD] is
meaningless; hence, the issue of a select command is blocked.