- 75 - 
 
[TERM_TOPOLOGY]=2Term-Dual). Therefore, the operation signals in the 
DIFL#2 is not generated in the RDIF. 
 
Figure 2.7-3 examples the PLC monitoring signals “DIFL-A,-B, and -C” are sent for the 
remote relays using sub-communication channels COM5-4,5,6 bits; communication application 
function (COMM_APPL) function provides the features of the sub-communication channel. In 
other words, the user should connect the PLC monitoring signals with PLC connection points 
“COM5-1,-2,-3_S”†. 
a. Sending frames for remote IEDs in IEEE C37.94 
b. Connections for sending  using PLC function† 
COMM_ APPL function (Function ID: 4A9001) 
 
Figure 2.7-3 Mapping for sending signals using COM5 bits 
†Note: For more information, see 
Chapter Relay application: Communication Application
. 
For applying N=3 frame, set Wide for scheme switch [CH*_COM_WIDTH]. 
 
  Reception of remote-DIFL-operation signal 
We should receive remote-operation signals at the local RDIF function. Figure 2.7-4 shows the 
RDIF  reception  logic:  PLC  connection  points  “R1.DIFL-A,-B,  -C_OP”  are  provided  for  the 
Remote-1_relay, the other PLC connection points “R2.DIFL-A,-B, -C_OP” are provided for the 
Remote-2_relay. The signals received from both remote-relays are ORed; then they are ANDed 
with  the  local  signals  provided  the  user  sets  On  for  scheme  switch  [DIFL-RDIF-EN]. 
Consequently, the local DIFL function begins to provide trip signals despite that the local DIFL 
function fails to operate.