- 1106 -
Setting procedure
The user should make the following steps in respective IEDs.
1) Set BI for the setting [Time Sync Src]; then set On for the setting [BI-SYNC].
2) Check BI is shown under the ActivSyncSrc, as shown in Figure 5.7-8.
3) Set a Data_ID for setting [BI_ID]. For example, as shown in the Figure 5.7-7, when
the user wishes to inject the signal at the BI1 on the IO#1 slot, the user should set
BI1(200B01 8001001111) for the setting [BI_ID].
4) Set a time adjuster for the setting [SYNC ADJ]. For example, set a value (e.g., 0.050s)
for setting [SYNC ADJ]. The setting is used when the clock function should be
synchronized before reaching the 1Hz square-wave due to the propagation or the
operating time on the BI circuit.
Clock
10:00 1/2
[Time] +
2012-11-21 10:00:05
[Format]
YYYY-MM-DD HH:mm:ss
[ActiveSyncSrc]
BI
Check “BI being shown under ActiveSyncSrc.
Figure 5.7-8 Time setting for BI
Table 5.7-3 Setting items for the BI Time synchronization
Setting item
Range
Contents
Setting example
Notes
TimeSyncSrc
SNTP / BI / IRIG-B
Selection of sync method
BI
BI-SYNC
Off /On
Operation of BI
On
BI_ID
[Preferred ID]
Signal monitoring point
200B01 8001001111
SYNC ADJ
0.050 to +0.050
Time adjust factor (in
sec.)
0.000
Leading the clock
+Delaying the clock