- 771 -
4.4.1 Select logic for SBO/DIR modes
The user should set the scheme switch [OPTR01-EN] to On prior to the OPTIM operation.
Figure 4.4-4 shows select logic in the OPTIM function.
Signal reception
IEC61850
Resetting OTs from the remote-end
Figure 4.4-4 Outline of select command for resetting
(i) Input point required mapping
Figure 4.4-5 shows the select logic when a “Select command (Reset)” signal enters the OPTIM
function. The logic has the input-point “OPTR01_CONTROL_REQ” for the reception. That is,
the input-point should be mapped for the IEC61850 communication. The function encounters
an operation failure if mapping is not performed correctly. We discuss how to map the input-
points for the IEC61850 communication in section 4.4.4.
OPTIM function (Function ID: 529001)
OPTR01_NSD_CSF
(529001 830C011F41)
Either “SBO mode” or “DIR mode”
(e.g., “ctlmodel” in IEC61850*)
“Automatic sequence control function
(AQEQ)§” in progress
To “Wait for a next command”
OPTR01_FSE_RCV
(529001 800C011F42)
Figure 4.4-5 Select logic for resetting intervals OT1 to OT4
‡Note: A “select condition” signal is provided from the select condition scheme. For more
information, see Figure 4.4-6.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
the automatic control. The OPTIM operation is blocked for the ASEQ function
being in the operation. For more information of the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.