Overvoltage protection for phase-to-neutral (OV)
The over voltage protection function for phase (OV) detects an over voltage condition that
phase-to-neutral voltage is larger than a setting and operates accordingly. The OV function
has two stages (elements; OV1 and OV2), which operate independently. The OV element has a
time delay characteristic; and the user can select either (1) independent (definite) time
characteristic delay or (2) dependent (inverse) time characteristic delay. The OV element is
configured both the setting of a pickup voltage (PU) and the setting of a drop-off voltage (DO).
To simplify the description, only OV1 is discussed, but the expression is applicable to the
OV2; hence, read the expression for OV1 as the OV2 unless a special explanation or instruction
has been provided.
─────────────────────────────────────────────────────────────────
Note: Several IED models do not have phase over-voltage protection features. To determine
whether the features are implemented in the IED or not, locate the IED ordering number; and
check the order number at G&T position referring to the comparison table below. For more
information, see
Appendix: Ordering
.
Table 2.21-1 Comparative table in respective ordering numbers
feature
Ordering No. at G&T
33
37
OV
Phase over-voltage protection
: Applicable NA: Not applicable