6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 915 -
Input
Output
Selection logic in TPOS01
Command Local-P1-Control
TPOS01-P1
ILK condition (“P1”) passed
ILK bypassing
1≥
ICB_STATE
[TPOS01-CTRAHMI]
SBO
TPOS01 function (Function ID: 513001)
SBO
DIR
&
&
1≥
&
0.1s
0
t
0.6s
0
t
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
Select condition
TPOS01_P1SL_BO_FL
(513001_8A04011DC4)
Select Failed
To BO connection
Select success
To Wait for a command
Select command
with ILK condition
Operate command
with ILK condition
For SBO operation
For DIR operation
To Wait for a next
command
Figure 4.9-9 Selection logic for P1-control at the IED locally in TPOS01
††
Note: The ILK function provides the operation criteria for P1-control”.
Note: Aselect condition signal is provided from the select condition scheme. For more
information, see Figure 4.9-20
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The TPOS01 operation is blocked for the ASEQ function when
it is in operation. For more information regarding the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
††
Note: To identify the input/output signals of the other TPOS logics, see Table 4.9-6,
Table 4.9-7 and Table 4.9-10.
Output signal to BO
When the select condition signal is true, the TPOS01 function can issue a “Select success”
signal at the output-point “TPOS01_P1SL_BO_FL”.
Note: The signal “TPOS01_P1SL_BO_FL is the same as the signal shown in Figure
4.9-3. If the input signal Local-P1-Control” is not true, the TPOS01 function
returns to the Wait for a command stage.
(v) Receiving “Select command P2-control” from the local-end.
Figure 4.9-10 outlines the reception of the select command P2-control from the local-end.