Toshiba GR200 Series - (i) Synchronism-relays (SyncRy1-dV, SyncRy1-df, SyncRy1-dθ); (i)-1 Voltage-variance (ΔV) (see Figure 4.6-3)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 800 -
Δ
Δ reducing
Δ increasing
Δ near
zero
V
r
V
i
V
i
V
i
V
i
Figure 4.6-4 Permissible ranges for connections between asynchronous networks
Note: Vr is the voltage on a running line.
Note: Vi is the voltage on an incoming line.
Table 4.6-3 Settings in SYNCHK_Ry1
Setting Name
Description
Default
Setting item or value
SyncRy1-Angle
Checking angle variance
30 degrees
0 to 75 degrees
SyncRy1-dV
Checking voltage variance
150V
0 to 150 V
SyncRy1-df
Checking frequency variance
1Hz
0.01 to 2 Hz
SyncRy1-TCB
Advance time for SYNCHK01
Seconds
SYNC01_TSYN
Sync check timer for loop system
10s
0.00 to 100.00 s
SyncRy1-dfEN
Diff. frequency for the checking SyncRy1 enable
Off
Off / On
(i) Synchronism-relays (SyncRy1-dV, SyncRy1-df, SyncRy1-dθ)
Synchronism-relays, SyncRy1-dV, SyncRy1-df, and SyncRy1- are provided; the setting
ranges for these relays are shown in Table 4.6-3.
Voltage-variance (ΔV) (see Figure 4.6-3)
The voltage-variance between Vr and Vi (
) is measured by the voltage-variance relay-
element having a setting [SyncRy1-dV]. If equation (4.6-3) is satisfied together with the
conditions stipulated in equations (4.6-2) and (4.6-3), the SyncRy1-dV relay determines that
the voltage-variance is inside the permissible range.

󰇟
OVR1
󰇠
(4.6-1)
󰇟OVI1󰇠
(4.6-2)
󰇟SyncRy1-dV󰇠
(4.6-3)