6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 902 -
4.8.8 Setting
DPOS01(Function ID: 512001)
Setting items
Range
Unit
Contents
Default
Note
Commo
n
DPOS-NELD
0 - 99
-
Number of Event lock detect time
10
DPOS-TELD
1 - 99
s
Timer of detect event lock
10
DPOS-TELR
1 - 99
s
Timer of recovery from event lock
10
DPOS01-EN
Off / On
-
DPOS01 switch for Device01
Off
Dev01
DPOS01-DEVNAME
[Preferred text]
-
item name of DPOS_Dev1
DPOS_Dev1
!
DPOS01-00NAME
[Preferred text]
-
state name of (0,0)state
Travelling0
!
DPOS01-01NAME
[Preferred text]
-
state name of (0,1)state
Off
!
DPOS01-10NAME
[Preferred text]
-
state name of (1,0)state
On
!
DPOS01-11NAME
[Preferred text]
-
state name of (1,1)state
Travelling1
!
DPOS01-UDFNAME
[Preferred text]
-
state name of undefined
Undefine
!
DPOS01-FLTNAME
[Preferred text]
-
state name of faulty
Faulty
!
DPOS01-DEVTYPE
1-Pole / 3-Pole /
switch
-
Device Type
1-Pole
DPOS01A-NOPSG
[Preferred signal]
-
Normally Open Signal of the single-pole or
phase A
Not assigned
DPOS01A-NOPSGI
Off / On
-
Signal inverse or not
Off
DPOS01A-NCLSG
[Preferred signal]
-
Normally Close Signal of the single-pole or
phase A
Not assigned
DPOS01A-NCLSGI
Off / On
-
Signal inverse or not
Off
DPOS01B-NOPSG
[Preferred signal]
-
Normally Open Signal of phase B
Not assigned
DPOS01B-NOPSGI
Off / On
-
Signal inverse or not
Off
DPOS01B-NCLSG
[Preferred signal]
-
Normally Close Signal of phase B
Not assigned
DPOS01B-NCLSGI
Off / On
-
Signal inverse or not
Off
DPOS01C-NOPSG
[Preferred signal]
-
Normally Open Signal of phase C
Not assigned
DPOS01C-NOPSGI
Off / On
-
Signal inverse or not
Off
DPOS01C-NCLSG
[Preferred signal]
-
Normally Close Signal of phase C
Not assigned
DPOS01C-NCLSGI
Off / On
-
Signal inverse or not
Off
DPOS01-OPC
And / Or
-
Normally Open contact grouping
And
DPOS01-CLC
And / Or
-
Normally Close contact grouping
Or
DPOS01-SPPEN
Off / On
-
Automatic event suppression function
Off
DPOS01-UDFEN
Off / On /
CHKONLY
-
undefined pallet check function
Off
DPOS01-UDFTIM
0.1 - 100.0
s
palette Undefined check timer
30.0
DPOS01-FLTEN
Off / On /
CHKONLY
-
faulty pallet check function
Off
DPOS01-FLTTIM
0.1 - 100.0
s
palette faulty check timer
30.0
DPOS01-CTREN
Off / On
-
control mode (control enable)
Off
DPOS01-CTRMENU
Off / On
-
control by MENU enable
Off
DPOS01-CTRAHMI
DIR / SBO
-
control action(Direct or SBO)by HMI
SBO
DPOS01-NSLBORD1
[Preferred signal]
-
select binary output read data(DataID)1 for no
direction select command
5120018903011DC0
DPOS01-NSLBORD2
[Preferred signal]
-
select binary output read data(DataID)1 for no
direction select command
5120018903011DC0
DPOS01-FSLBORD
[Preferred signal]
-
select binary output read data(DataID) for off
direction select command
5120018A03011DC4
DPOS01-OSLBORD
[Preferred signal]
-
select binary output read data(DataID) for on
direction select command
5120018603011DC6
DPOS01-FEXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
off direction execute command
Not assigned
DPOS01-OEXBORD
[Preferred signal]
-
execute binary output read data(DataID) for
on direction execute command
Not assigned