4.2.5 Measurement of operation intervals
The DPSY01 function can measure operation intervals (OT1 to OT4)†; the intervals OT1 to
OT2 can represent the period of time when a switch changes from “Closed” to “open”. In the
DPSY01 function the operation period is grouped into sub-time periods, as shown in Table
4.2-28. The user should set scheme switch [DPSY01-OPETMEN] to On.
Table 4.2-28 Intervals measured in the DPSY01 function
Intervals
Trigger
Events for measurement
OT1
Start
Signal “DPSY01_FEX_BO” sensed
End
Switch status is changed from Closed to
“Intermediate”
OT2
Start
Switch status “Intermediate” sensed
End
Switch status is changed from “Intermediate” to
Open
OT3
Start
Signal “DPSY01_OEX_BO” sensed
End
Switch status is changed from Open to
“Intermediate”
OT4
Start
Switch status “Intermediate” sensed
End
Switch status is changed from “Intermediate” to
Closed”
Note: The function operation time measurement is also available in the DPSY02
function.
Signal “DPSY01_FEX_BO
OT1
OT2
Sensing Intermediate state
Device status for Open
Closed
Intermediate
Open
Figure 4.2-37 Two intervals (OT1 and OT2) for Open-control
Signal “DPSY01_OEX_BO
OT3
OT4
Un sensed period
Device status for Closed
Open
Intermediate
Closed
Figure 4.2-38 Two intervals (OT3 and OT4) for Closing-control
The user can clear the operation interval (OT1 to OT4) by key-operation of the Operation
time sub-menu (Figure 4.2-39) or operation from the remote-end. See chapter
User interface: