Toshiba GR200 Series - 9.10 Setting

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1204 -
Setting
Metering settings in MES (Function ID: 710001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
Display Value
Primary/Secondary
Display selection of primary or secondary
Primary
Power
Send/Receive
Power flow definition (Supply or absorb)
Send
Current
Lead/Lag
The angle compared with the voltage
Lead
PF Sign
AP/AP+RP
Decision of the sign of the power factor
AP+RP
I-Valid Level
0.10 to 5.00
%
Cutting off small entering current
4.00
V-Valid Level
0.10 to 5.00
%
Cutting off small applied voltage
0.30
I-Display Unit
A/kA
Current shown in Ampere or Kilo-Ampere
kA
V-Display Unit
V/kV
Voltage shown in Volt or Kilo-Volt
kV
P-Display Unit
kW/MW
Active power shown in Kilo- or Mega-watt
MW
Q-Display Unit
kvar/Mvar
Reactive power shown in Kilo- or Mega-var
Mvar
S-Display Unit
kVA/MVA
Apparent power shown in Kilo- or Mega-
VA
MVA
Statistics settings in MES (Function ID: 710001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
Wh-Display Unit
kWh/MWh
Watt-hour shown in Kilo- or Mega-Wh
MWh
varh-Display Unit
kvarh/Mvarh
Var-hour shown in Kilo- or Mega-varh
Mvarh
Demand settings in MES (Function ID: 712001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
Demand_period
1min / 5min /
10min / 15min /
30min / 60min
Period of demand calculation
10min
Dead-band setting in MES (Function ID: 710001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
ISD
0.00 to 50.00
%
Sending Dead Band in current
5.00
VSD
0.00 to 50.00
%
Sending Dead Band in voltage
0.60
P/Q/SSD
0.00 to 50.00
%
P/Q/S Sending Dead Band
5.00
PFSD
0.00 to 1.00
PF Sending Dead Band
0.02
FSD
0.00 to 50.00
%
F Sending Dead Band
0.50
Wh/varhSD
0.0 to 999.9
Wh/varh Sending Dead Band
1.0
PhaseSD
0.0 to 90.0
deg
Phase Sending Dead Band
0.5
PeriodSD
0 to 4
Period of Sending Dead band
0
dVSD
0.00 to 50.00
%
dV Sending Dead Band
0.60
Setting of Test in MES (Function ID: 710001)
Setting item
Range
Unit
s
Contents
Default
setting value
Notes
Commercial Test
OFF / ON
Commercial Test Switch
OFF / ON