-  280  - 
 
2.18.1  Thermal state determination 
THM simulates the change of thermal state using an algorithm; THM can detect an overload 
condition. Thermal state (θ) is determined with the following equation: 
  
   
where 
I
 is the load current applied; 
I
AOL
 
is the allowable overload current;  is the thermal time 
constant. The value of  is set using setting [TTHM]. 
 
Thermal state 0% is the cold state, whereas 100% reflects the thermal limit—which is 
the point at which no further temperature rise can be tolerated safely and the system should 
be disconnected. The thermal limit for any given system is subject to setting [THM], which 
determines the value of overload current. The THM signals a trip when the value of θ is at 
100%. 
 
THM  determines 
I
  using  the  positive-sequence  current  (I
1
)  and  negative-sequence 
current (I
2
) using Equation (2.18-2); and operates according to the characteristics defined in 
IEC 60255-149† when the user has set scheme switch [THM-Itype] Equivalent. 
where, 
q:  Unbalance factor; the unbalance factor is used for motor/generator protection; the 
user should set q=0 when setting [THM-q] except when it is applied to 
motor/generator protection. 
 
†Note: If the user prefers to use the thermal characteristic for the THM function specified 
in IEC 60255-8, set Max phase for the scheme switch [THM-Itype]. In this case, 
THM is determined using the largest of the three-phase currents. 
 
The period of time for a trip to occur depends not only on the degree of overload, but also 
on the degree of load current as far as reaching the overload state. The period of the trip, that 
is, depends on whether the  overload is  applied from ‘cold’ or ‘hot’. THM has thresholds for 
alarm and trip; hence, the two thresholds exist independently.