Toshiba GR200 Series - 14.5 Setting

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1513 -
Setting
Setting of TEST (Function ID: 201301)
Setting items
Range
Unit
Contents
Default
Note
TestFlag-EN
Off / On
Change test flag on Protocol
On
A.M.F.
Off / On
Supervisor function use or not
On
Setting of CMMSLV (Function ID: 300001)
Setting items
Range
Unit
Contents
Default
Note
S-TestFlagCancel
Off / On
Cancelling test flag of slave communication
Off
GOSNDBLK
Off / On
GOOSE publishing block
Off
GOSUBBLK
Off / On
GOOSE subscription block
Off
Setting for Protection function test
Setting items
Range
Unit
Contents
Default
Note
1A rated
5A rated
CLP-Test
Off / STATE0 / STATE3
Forcibly changing to CLP state
Off
Local-Test
Off / On
Local Test Switch
Off
Loop-Test
Off / On
External Loop Test Switch
Off
Open 1
Off / On
CH1 Open Test Switch
Off
Open 2
Off / On
CH2 Open Test Switch
Off
DIFL-STUB-Test
Off / On
Forcibly establishing the stub condition
Off
ZS-Test.CTRL
Off / On
ZS-test mode use or not use
Off
ZS-Offset.CTRL
Normal / Offset / Non-
Offset
ZS-offset mho use or not use
Normal
ZS-Test.XAngle
Off / On
ZS-reactance test mode use or not use
Off
ZG-Test.XAngle
Off / On
ZG-reactance test mode use or not use
Off
THM-Test
Off / On
To utilize the setting[THM-IP]
Off
THM-IP
0.00 -1.00
0.00 -5.00
Previous load current for thermal testing
0.00
SOTF-Test
Off / On
Forcibly establishing the cold load condition
Off
UV-Test
Off / On
Not to execute UV block function
Off
UVS-Test
Off / On
Not to execute UVS block function
Off
SHOTNUM-Test
Off / S1 / S2 / S3 / S4 / S5
/ S6
Auto reclose test shot number
Off
SYNC01-Test
Off / On
SYNC DEV1 synchronism check test mode
Off
SYNC02-Test
Off / On
SYNC DEV2 synchronism check test mode
Off
Setting of BIO_FORCE (Function ID: 240101)
Setting items
Range
Unit
Contents
Default
Note
SLOT*-BIxx-SET
Normal / Off / On
Test switch for BI circuit xx at slot “IO#*”
Normal
SLOT*-BOxx-SET
Normal / Off / On
Test switch for BO circuit xx at slot “IO#*”
Normal