EasyManua.ls Logo

Toshiba GR200 Series - (i) Calculation Principle; (i)-1 Calculation on two-terminal application; (i)-2 Calculation on three-terminal application

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 380 -
(i) Calculation Principle
Calculation on two-terminal application
Figure 2.32-1 shows two IEDs exist at the end of the line GH. Voltages due to the fault are
calculated by Equation (2.32-1) and Equation (2.32-2).
Figure 2.32-1 IED G and IED H on line GH

(2.32-1)
󰇛
󰇜

(2.32-2)
where,
V
G
: Voltage at IED G
I
G
: Current at IED G
V
H
: Voltage at IED H
I
H
: Current at IED H
 Distance ratio of GF to GH
V
f
: Voltage at fault point
Z
GH
1
: Impedance on line GH
Substituting Equation (2.32-1) for Equation (2.32-2)
gives,


󰇛
󰇜
(2.32-3)
The distance ratio () is also calculated with the differential current (Id) because the net
currents at the IED G and the IED H are equal to the differential current (Id= I
G
+I
H
):


(2.32-4)
1
Note: User should set the Z
GH
into Line1_Element. For further information, see section
2.32.5(ii). For setting methods, see section 2.32.6(iii).
Calculation on three-terminal application
The principle mentioned above is also applicable for the operation of three terminals, as shown
in Figure 2.32-2. Note that one of three calculations (Calc. 1 to 3) determines the fault location.
Bus G
TT
Bus H
TT
V
G
I
G
Fault
TT
V
f
Z
GH
× Z
GH
IED G
TT
(1)× Z
GH
IED H
TT
F
V
H
I
H

Table of Contents

Related product manuals