EasyManua.ls Logo

Toshiba GR200 Series - (ii) Output signal required to map; (iii) Select condition

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 772 -
*Note: The OPTIM function can run on either the SBO mode or the DIR mode using a
signal ctlmodel when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.
(ii) Output signal required to map
The OPTIM function can issue a Select success signal at the output point
OPTR01_NSD_CSF, when the OPTIM function can decide that the input signal Select
command (Reset) is true. If the OPTIM function decides that the Select command (Reset) is
not true, the OPTIM function returns to the Wait for a command stage.
(iii) Select condition
Figure 4.4-6 shows the select condition logic in the OPTIM function.
Select condition
OPTIM function (Function ID: 529001)
To selection logic
Control hierarchy (e.g. 43RL) (PLC connection point) *5
IED serious error detected
[OPTR1_EN]
On
Users must setup this condition correctly
Function Automatic sequence control is in progress
CBK_STATE
Command blocking*1
Double Command Blocking detected*2
Other devices traveling detected*3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
OPTR01_CTRL_RIGHT
529001 820C01ED50
SERI_ERR
&
&
1
Unmatched condition detected *4
Figure 4.4-6 Select condition logic in the OPTIM function
*6
*1
Note: The command blocking disables any operation except for itself: the
command blocking is stated with CBK in a software controller (SOFTSW). The
IEC61850 defines the command blocking as CmdBlk. For more information on
CBK, see Chapter
Control and monitoring application: Software switch control
function
. See the signal CBK_STATE of Table 4.4-2.
*2
Note: “Double Command Blocking (DCB) is operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
should program it using the GR-TIEMS. The DCB operating signal is denoted as
DCB RCV_OR in Table 4.4-2. For more information, see Chapter
Control and
monitoring application: Common controls
.
*3
Note: If events “device-travelling” are detected in the CMNCTRL function, we can
see that some statuses of the devices are being changed by other operators. Thus,
the IED should stop any operation while the events are being detected. The
detecting signal is denoted by “Traveling OR in Table 4.4-2.

Table of Contents

Related product manuals