EasyManua.ls Logo

Toshiba GR200 Series - (i)-2 Output signal to BO; (ii) Receiving “Cancel” from the local-end; (ii)-1 Input signal generated at the local-end

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 687 -
Output signal to BO
The DPSY01 function can issue a Success to cancel signal at the monitoring point
DPSY01_CC_SS, when the DPSY01 function has determined that the Remote-cancel signal
is true. Another Operation failed signal is issued at monitoring point DPSY01_CC_FS if
the DPSY01 function is able to determine that the Remote-cancel signal is not true.
(ii) Receiving “Cancel” from the local-end
Figure 4.2-16 outlines the reception of the cancel command from the local-end.
Press cancel
command
Cancel from the local-end
Do nothing
Cancel
decision
Success
Failed
Cancel logic
Wait for a command
Operate logic
Operate command
Operate logic
Select logics
Selecting Open from the remote-end
Selecting Closing from the remote-end
Selecting Open from the local-end
Selecting Closing from the local-end
Selecting Closing by the PLC function
Selecting Open by the PLC function
Cancel from the remote end
Wait for a next command
Figure 4.2-16 Outline of cancel command from the local-end
Input signal generated at the local-end
Figure 4.2-17 depicts the cancel logic when a Cancel command (Local-cancel)” signal is applied
to the DPSY01 function. The signal is generated when the Cancel key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
Local-cancel signal, the logic is able to output a result signal, provided that the cancel
condition checking is satisfied.
DPSY01 function (Function ID: 511001)
DPSY01_ CC_SS
(511001 8602011E95)
Cancel command
Input
Output
Cancel logic in DPSY01
Cancel condition
&
&
Successes to cancel
Operation Failed
DPSY01_CC_FS
(511001 8702011E96)
Command Local-cancel
Do nothing
To Wait for a command
Figure 4.2-17 ‘Cancel’ from the front panel

Table of Contents