Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1417 -
Oct.
Item
Value
Remarks
4
Start
68H
5
Control field
08H+ACD+
DFC
6
Address
1-254
Setting from the relay
7
Type identification (Type ID)
1
Customized by GR-TIEMS
8
Variable structure qualifier
81H
9
Cause of transmission (COT)
20/21
Customized by GR-TIEMS
10
Common address of ASDU
1-254
Linked with Address setting
11
Function type (FUN)
0-255
Customized by GR-TIEMS
12
Information number (INF)
0-255
Customized by GR-TIEMS.
Answer back of receiving
command INF
13
Double point information (DPI)
1/2
Answer back of receiving
command DCO
14
Millisecond (low)
0-59999
15
Millisecond (high)
16
Minutes + Invalid flag (MSB)
0-59+80H
17
Hours + Summer time flag (MSB)
0-23+80H
18
Supplementary information (SIN)
0-255
Answer back of receiving
command RII
19
Checksum
20
End
16H
Any comment with maximum 16 characters can be entered. This setting does not affect
the function in the IEC 60870-5-103 communication.
Description
Any comment with maximum 16 characters can be entered. This setting does not affect the
function in the IEC 60870-5-103 communication.
Type ID
Type ID=20 (General command) is fixed.
INF
Information number (INF) of the frame is set. The INF can be set to 0 to 255. When the
standard frame is provided, the INF according to the standard is recommended. If the
frame out of standard is provided, the INF should be set referring Table 11.4-12 and the
appendix.
Table 11.4-12 INF category of Monitor direction
INF
Category
0 to 15
system functions
16 to 31
status
32 to 239
not used
240 to 255
generic functions
Note: For more information, see
Appendix: IEC 60870-5-103 interoperability
.