6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 404 -
Fault Locator (Function ID: 496001) at Common
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
FL_Z0B_R
0.00 -
1000.00
0.00 -
200.00
-
Zero sequence back source impedance at
remote terminal
10.00
2.00
Unit
FL_1Line_km
0.0 - 500.0
km
Line1 length (km)
50.0
FL_1Line_mile
0.0 - 310.0
mil
es
Line1 length (mile)
31.0
FL_2Line_km
0.0 - 500.0
km
Line2 length (km)
50.0
FL_2Line_mile
0.0 - 310.0
mil
es
Line2 length (mile)
31.0
FL_3Line_km
0.0 - 500.0
km
Line3 length (km)
50.0
FL_3Line_mile
0.0 - 310.0
mil
es
Line3 length (mile)
31.0
2.32.8 Data ID
Signal monitoring point
FL-AZ (Function ID: 496001)
Element ID
Name
Description
8000101349
FLTFLAG
Fault locator update flag
3100101348
FLTLOOP
Fault loop
3100101005
FLTQUALITY
Quality of fault locator
Connection point in PLC logic
FL-AZ (Function ID: 496001)
Element ID
Name
Description
310022EC66
FLAZ_LOCF
Fault locate start signal (Local and remote end data, forward)
310022EC67
FLAZ_LOCR
Fault locate start signal (Local and remote end data, reverse)
310022EC64
FLAZ_RECF
Record start signal (Local and remote end data, forward)
310022EC65
FLAZ_RECR
Record start signal (Local and remote end data, reverse)
310022EC62
FLZ_LOCF
Fault locate start signal (Only local end data, forward)
310022EC63
FLZ_LOCR
Fault locate start signal (Only local end data, reverse)
310022EC60
FLZ_RECF
Record start signal (Only local end data, forward)
310022EC61
FLZ_RECR
Record start signal (Only local end data, reverse)

Table of Contents

Related product manuals