- 666 -
4.1.6 Setting
SPOS01 (FunctionID:510001)
Setting items
Range
Unit
Contents
Default
Note
Commo
n items
SPOS-NELD
0 - 99
-
Number of Event lock detect time
10
SPOS-TELD
1 - 99
s
Timer of detect event lock
10
SPOS-TELR
1 - 99
s
Timer of recovery from event lock
10
SPOS01-EN
Off / On
-
SPOS01 switch for Device01
Off
DEV01
items
SPOS01-DEVNAME
[Preferred text]
-
item name of Dev1
SPOS_Dev1
!
SPOS01-OFFNAME
[Preferred text]
-
state name of state(off)
Off
!
SPOS01-ONNAME
[Preferred text]
-
state name of state(on)
On
!
SPOS01-NOPSG
[Preferred Signal]
-
Normally Open Signal of Dev1
Not Assigned
SPOS01-SPPEN
Off / On
-
Automatic event suppression function
Off
SPOS01-CTREN
Off / On
-
control mode (control enable)
Off
SPOS01-CTRMENU
Off / On
-
control by MENU enable
Off
SPOS01-CTRAHMI
DIR / SBO
-
control action(Direct or SBO)by HMI
SBO
SPOS01-SLBORD
[Preferred Signal]
-
select binary output read data(DataID)
5100018501011F76
SPOS01-OEXBORD
[Preferred Signal]
-
on direction execute binary output read
data(DataID)
Not Assigned
SPOS01-FEXBORD
[Preferred Signal]
-
off direction execute binary output read
data(DataID)
Not Assigned
SPOS01-OFEXBORD
[Preferred Signal]
-
on/off direction execute binary output read
data(DataID)
Not Assigned
SPOS01-LGCTRCON
FixedLogic /
PLC
-
Change logic about control condition
FixedLogic
SPOS01-LGSLFFCT
FixedLogic /
PLC
-
Change logic about select fail factor
FixedLogic
SPOS01-LGEXFFCT
FixedLogic /
PLC
-
Change logic about execute command fail
factor
FixedLogic
SPOS01-LGFEXOT
FixedLogic /
PLC
-
Change logic about off direction execute
output
FixedLogic
SPOS01-LGCNFFCT
FixedLogic /
PLC
-
Change logic about cancel command fail factor
FixedLogic
SPOS01-PLSM
Fix / Var / Latch
-
pulse mode
Var
SPOS01-CPW
0.1 - 50.0
s
control pulse width
1.0
SPOS01-RST
1.0 - 100.0
s
response check timer
30.0
SPOS01-APBD
Process / Bay
-
status change origin
Process
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The SPOS function is available for a 2
nd
Device and other devices. We have
omitted the others because their setting tables are the same as the 1
st
device table
with the exception of the device number.