- 8 - 
 
fault arc is considered to be almost equivalent to pure resistance. But if the phase of a current 
that flows into a fault point from the remote end is different from the phase of the local current, 
the voltage at the fault will have a phase angle difference with respect to the local current, 
producing  a  measuring  error  in  the  distance  relay  with  the  principle  of  measuring  the 
reactance  component.  The  existence  of  a  zero-sequence  current  on  the  protected  line  and 
adjacent line can also cause errors in the earth fault relay. The zero-sequence current normally 
acts  in  the  direction  of  relay  underreaching  due  to  the  effect  of  the  induced  voltage.  The 
compensation method  will be described  in detail in the  next  section. The earth  fault relay 
contains  more  errors  than  the  phase  fault  relays  even  with  these  compensation  methods. 
Therefore, the earth fault relays are usually set with a greater margin than the phase fault 
relays. 
 
Regarding measuring errors in the relay, it is also necessary to consider hardware errors 
in the relay itself, errors introduced by coupling capacitor voltage transformers (CCVT), and 
transient overreach errors caused by the DC component of the fault current. For the GR200 
series relays, the errors are defined to be less than 5%. 
 
(iii)  Detection of power swing and out-of-step 
Power swings occur when the output voltages of generators at different points in the power 
system slip relative to each other, which result in system instabilities that may be caused by 
sudden changes in load magnitude or direction, or by power system faults and their subsequent 
clearance. During the course of such a power swing, the impedance seen by a distance relay 
may move (relatively slowly) from the load area into the operating characteristic of the distance 
protection. In fact, this phenomenon appears to the distance protection measuring elements 
like a three phase fault condition and may result in tripping if no countermeasure is applied. 
Most power swings are transient conditions from which the power system can recover after a 
short interval, and distance protection tripping is therefore highly undesirable in such cases. 
GR200  series  relay  provides  the  block  function  for  power  swing  (PSB)  so  that  preventing 
unwanted  tripping  is  possible  during  the  power  swing.  Figure  1.1-5  illustrates  the  typical 
impedance locus as seen by the distance relay during the transient power swing.