EasyManua.ls Logo

Toshiba GR200 Series - 4.6.7 Setting

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 818 -
4.6.7 Setting
Synchronism (Function ID: 560001)
Setting items
Range
Unit
Contents
Default
Note
SYNC01_SYNCHK1EN
Off / On
-
SYNC DEV1 synchronism check switch
Off
SYNC02_SYNCHK2EN
Off / On
-
SYNC DEV2 synchronism check switch
Off
SYNC
01
SYNC01_TLRDIDRLI
0.00 - 5.00
s
V check timer(Live Run. & Dead Incom., Dead
Run. & Live Incom.)
5.00
SYNC01_TDRDI
0.00 - 5.00
s
V check timer(Dead Run. & Dead Incom.)
5.00
SYNC01_TSYN
0.00 - 100.00
s
synchronism check timer(Loop)
10.00
SYNC01_TSYN2
30 - 1800
s
Synchronism check time up
60
SYNC01_Split_EN
Off / On
-
SYNC DEV1 split synchronism check mode
enable
Off
SYNC01_LRDIEN
Off / On
-
SYNC DEV1 Live Run. & Dead Incom. close
mode enable
On
SYNC01_DRLIEN
Off / On
-
SYNC DEV1 Dead Run. & Live Incom. close
mode enable
On
SYNC01_DRDIEN
Off / On
-
SYNC DEV1 Dead Run. & Dead Incom. close
mode enable
On
SYNC
02
SYNC02_TLRDIDRLI
0.00 - 5.00
s
V check timer(Live Run. & Dead Incom., Dead
Run. & Live Incom.)
5.00
SYNC02_TDRDI
0.00 - 5.00
s
V check timer(Dead Run. & Dead Incom.)
5.00
SYNC02_TSYN
0.00 - 100.00
s
synchronism check timer(Loop)
10.00
SYNC02_TSYN2
30 - 1800
s
Synchronism check time up
60
SYNC02_Split_EN
Off / On
-
SYNC DEV2 split synchronism check mode
enable
Off
SYNC02_LRDIEN
Off / On
-
SYNC DEV2 Live Run. & Dead Incom. close
mode enable
On
SYNC02_DRLIEN
Off / On
-
SYNC DEV2 Dead Run. & Live Incom. close
mode enable
On
SYNC02_DRDIEN
Off / On
-
SYNC DEV2 Dead Run. & Dead Incom. close
mode enable
On

Table of Contents