- 542 -
2.38.7 Setting
PROT_COMMON (Function ID: 48A001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
UVLS
5.0 - 130.0
V
UV phase-phase relay operating value
77.0
UVLG
5.0 - 130.0
V
UV phase-ground relay operating value
45.0
OCD
0.05 -
0.20
0.25 -
1.00
A
OCD relay operating value
0.10
0.50
CB
CB-System
1CB / 2CB
-
Single CB or One-and-a-half CB system
1CB
CB1-Contact
NO / NC / Both
-
Kind of injected CB contact
NO
CB2-Contact
NO / NC / Both
-
Kind of injected CB2 contact
NO
TCBLOSPH
0.00 - 0.10
s
CB loss phase time
0.03
CB-SV
Off / On
-
CB contact supervisor enable
Off
TCBSV
0 - 100
s
CB contact supervisor time
10
DS
DS-Contact
NO / NC / Both
-
Kind of injected DS contact
NO
DS-SV
Off / On
-
DS contact supervisor enable
Off
TDSSV
0 - 100
s
DS contact supervisor time
60
DL
DLDbyUV
Off / On
-
Dead line detection by under voltage
Off
DLDbyCB
Off / On
-
Dead line detection by CB open
Off
TDLD
0.00 - 300.00
s
Dead line detection timer
10.00
UserLogicSW1
S1 / S2 / S3
-
User Logic Switch for General purpose
S1
UserLogicSW2
S1 / S2 / S3
-
User Logic Switch for General purpose
S1
UserLogicSW3
S1 / S2 / S3
-
User Logic Switch for General purpose
S1
UserLogicSW4
S1 / S2 / S3
-
User Logic Switch for General purpose
S1