6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 861 -
DPOS01 function (Function ID: 512001)
DPOS01_ CC_SS
(512001_8603011E95)
DEV01_CONTROL_REQ
Cancel command
Command Remote-cancel
510001_7001016D08
510001 7001016D08
Input
Output
Cancel logic in DPOS01
Cancel condition
&
&
Successes to cancel
Operation Failed
DPOS01_CC_FS
(512001_8703011E96)
Do nothing
To Wait for a command
Figure 4.8-15 ‘Cancel’ from the remote-end in DPOS01
Note: The cancel conditionlogic shall be seen in Figure 4.8-18.
(ii) Receiving “Cancel” from the local-end
Figure 4.8-16 depicts the cancel command procedure for a cancel command initiated from the
local-end.
Press cancel
command
Cancel from the front panel
Do nothing
Cancel
decision
Success
Failed
Cancel logic
Wait for a command
Operate logic
Operate command
Operate logic
Select logics
Selecting Off from remote-end
Selecting On from remote-end
Selecting Off from front panel
Selecting On from front panel
Selecting On by the PLC function
Selecting Off by the PLC function
Cancel from the remote end
Wait for a next command
Figure 4.8-16 Outline of ‘cancel command from the local-end
Input signal generated at the local-end
Figure 4.8-17 depicts the cancel logic when a Cancel command (Local-cancel)” signal is applied
to the DPOS01 function. The signal is generated when the Cancel key is pressed on the IED
front panel; the user is not required to take account of mapping. When the logic receives the
Local-cancel signal, the logic ia able to output a result signal, provided that the cancel
condition checking is satisfied.