6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 961 -
Signal Number
Signal Name
Description
513001 8A04181F8B
TPOS24_SLD_CSCN
TPOS24 counter selected
Table 4.9-24 Mapping points
Signal Number
Signal Name
Description
513001 7004016D09
DEV01_ALLCNT_REQ
TPOS01 counter correction request for summation counter value
513001 7004026D09
DEV02_ALLCNT_REQ
TPOS02 counter correction request for summation counter value
513001 7004036D09
DEV03_ALLCNT_REQ
TPOS03 counter correction request for summation counter value
513001 7004186D09
DEV24_ALLCNT_REQ
TPOS24 counter correction request for summation counter value
513001 7004016D0A
DEV01_P1CNT_REQ
TPOS01 counter correction request for P1 counter value
513001 7004026D0A
DEV02_P1CNT_REQ
TPOS02 counter correction request for P1 counter value
513001 7004036D0A
DEV03_P1CNT_REQ
TPOS03 counter correction request for P1 counter value
513001 7004186D0A
DEV24_P1CNT_REQ
TPOS24 counter correction request for P1 counter value
513001 7004016D0B
DEV01_P2CNT_REQ
TPOS01 counter correction request for P2 counter value
513001 7004026D0B
DEV02_P2CNT_REQ
TPOS02 counter correction request for P2 counter value
513001 7004036D0B
DEV03_P2CNT_REQ
TPOS03 counter correction request for P2 counter value
513001 7004186D0B
DEV24_P2CNT_REQ
TPOS24 counter correction request for P2 counter value
513001 7004016D0C
DEV01_P3CNT_REQ
TPOS01 counter correction request for P3 counter value
513001 7004026D0C
DEV02_P3CNT_REQ
TPOS02 counter correction request for P3 counter value
513001 7004036D0C
DEV03_P3CNT_REQ
TPOS03 counter correction request for P3 counter value
513001 7004186D0C
DEV24_P3CNT_REQ
TPOS24 counter correction request for P3 counter value
Table 4.9-25 PLC connection points for control hierarchy
Signal Number
Signal Name
Description
M/O
513001 800401ED5A
TPOS01IN_TMP_41
TPOS01 control hierarchy condition(PLC#1) for counters
M
513001 800402ED5A
TPOS02IN_TMP_41
TPOS02 control hierarchy condition(PLC#1) for counters
M
513001 800403ED5A
TPOS03IN_TMP_41
TPOS03 control hierarchy condition(PLC#1) for counters
M
513001 800418ED5A
TPOS24IN_TMP_41
TPOS24 control hierarchy condition(PLC#1) for counters
M
(v) Setting name
Table 4.9-26 Setting for pulse counter in TPOSxx
Setting Name
Description
Default
Setting item or value
TPOSxx-P1CNTS
Mode selection of the counter in P1-control
*user-preferred
NA / C-On / C-Off / C-OnOff
TPOSxx-P2CNTS
Mode selection of the counter in P2-control
*user-preferred
NA / C-On / C-Off / C-OnOff
TPOSxx-P3CNTS
Mode selection of the counter in P3-control
*user-preferred
NA / C-On / C-Off / C-OnOff