6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 882 -
(i) Receiving “change value for counter” from the remote-end
Mapping of Input signal required
Figure 4.8-34 depicts the logic when a command change value for counter is received at the
DPOS01 logic. With regard to a three-phase counter, the input-point
“DEV01_3PH_CONTROL_REQ” is used. With regard to a phase-A counter, the input-point
“DEV01_APH_CONTROL_REQ” is used. For phase-B and phase-C, the input-points
“DEV01_BPH_CONTROL_REQ” and “DEV01_CPH_CONTROL_REQ” are used.
DPOS01 function (Function ID: 512001)
Operate Command
DEV01_3PH_REQ
Command change value for counter
512001_7003016D09
&
DPOS01_SLD_CSCN
(512001 8A03031F86)
Input
Output
Operate logic in DPOS01
Operate condition
Figure 4.8-34 Changing counter value for three-phase
with operation from the remote-end in
DPOS01
Note: The operate condition signal is provided from the operate condition logic of
Figure 4.8-36.
Note: The user can apply other counter change commands for phase-A, -B, and C as
shown in Table 4.8-23. The resultant signals for the other DPOS02-72 logics are
shown in Table 4.8-24.
Output signal to BO
The DPOS01 function can issue a “Result” signal at output point DPOS01_SLD_CSCN”.
(ii) Receiving “change value for counter” from the local-end
Input signal from the front panel
Figure 4.8-35 depicts the logic when a change value for counter command is provided in the
DPOS01 function. The command is provided from the sub-menu, as shown in Figure 4.8-33.
DPOS01 function (Function ID: 512001)
DPOS01_SLD_CSCN
(512001 8A03031F86)
Input
Output
Operate logic in DPOS01
Command Change value
Figure 4.8-35 Changing counter value by operation from the front panel in DPOS01
Output signal to BO
The DPOS01 function can issue a “Result” signal at output point DPOS01_SLD_CSCN”.